Input Rating Voltage Frequency Voltage range Power Factor THDi 3000VA 220V, 230V, 240V, 1Ø 2Wires 40~70Hz 176-300 VAC at 100% load, 110-300 VAC at 50% load >99% <5% Ouput Active Power @ PF=0.9 Voltage (on battery) Frequency (on battery) Transfer Time Efficiency UPS Design Technology Output Wave Form Total Harmonic distortion (THD) Crest Factor 2700W 220V, 230V, 240V, +/-1% (selectable output voltage), 1Ø 2Wires 50/60 Hz +/-0.2% 0 ms 93% Online double conversion design Pure Sinewave ≤3% (linear load), ≤5% (non linear load) 3:1 Protection Overload Protection Short Circuit Protection 110% for 10min, 130% for 1min, >130% for 3sec UPS output cuts off immediately using input fuse/circuit breaker protection System Display LCD indicators Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators Alarm Battery mode Low battery Overload Fault Sounding every 4 second Sounding every second Sounding twice every second Continuously sounding Battery Battery Type Typical Recharge Time DC Voltage Charging Current Back up time(1/2 Load) 12V 9Ah 4 hours to 90% Full capacity 24VDC 1A 10~15 min depending on load Communication USB or RS-232 SNMP* Compatibility Interface with power management software Power Management from SNMP manager and web browser Supports Windows family, Linux, Unix and Mac Physical W x D x H mm Net Weight Kgs(lbs) 190x421x318mm 27.6Kg Environment Operating Temperature Storage Temperature Altitude Audible noise Relative Humidity 0 – 40 °C / 32 ~ 104°F -20 ~ 50°C / -4 ~ 122°F 1,500 meters max <50dBA at 1 Meter 20 to 90% humidity (non-condensing) Standards & Certifications Performance Safety EMC (EMS / EMI) Design, production, & services Environment Marking & Certifications EN50091-3/IEC 62040-3 UL 1778, CE, EN 50091-1,EN 60950 (RD/), IEC 60950 IEC 61000-4-2/-3/-4/-5/-6/-8/-11, IEC 61000-3-2/-3,FCC Part 15, CISPR 22, EN 50091-2/IEC62040-2 Class A, EN 55022/B,FCC 47 part 15 – Subpart B – ISO 9001 ISO 14001 certified company CE, TUV/GS, UL, cUL, c-Tick